| A security issue exists within DataMosaix™ Private Cloud, allowing attackers to bypass MFA during setup and obtain a valid login-token cookie without knowing the users password. This vulnerability occurs when MFA is enabled but not completed within a 7-day period. |
| A security issue exists within 432ES-IG3 Series A, which affects GuardLink® EtherNet/IP Interface, resulting in denial-of-service. A manual power cycle is required to recover the device. |
| A security issue exists within the Studio 5000 Logix Designer add-on profile (AOP) for the ArmorStart Classic distributed motor controller, resulting in denial-of-service. This vulnerability is possible due to the input of invalid values into Component Object Model (COM) methods. |
| A local code execution security issue exists within Studio 5000® Simulation Interface™ via the API. This vulnerability allows any Windows user on the system to extract files using path traversal sequences, resulting in execution of scripts with Administrator privileges on system reboot. |
| A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault. |
| A security issue exists due to improper handling of CIP Class 32’s request when a module is inhibited on the 5094-IF8 device. It causes the module to enter a fault state with the Module LED flashing red. Upon un-inhibiting, the module returns a connection fault (Code 16#0010), and the module cannot recover without a power cycle. |
| A vulnerability exists in the Rockwell Automation Emulate3D™, which could be leveraged to execute a DLL Hijacking attack. The application loads shared libraries, which are readable and writable by any user. If exploited, a malicious user could leverage a malicious dll and perform a remote code execution attack. |
| A denial-of-service security issue exists in the affected product and version. The security issue is caused through CIP communication using crafted payloads. The security issue could result in no CIP communication with 1715 EtherNet/IP Adapter.A restart is required to recover. |
| Studio 5000 Logix Designer 30.01.00 contains an unquoted service path vulnerability in the FactoryTalk Activation Service that allows local users to potentially execute code with elevated privileges. Attackers can exploit the unquoted path in C:\Program Files (x86)\Rockwell Software\FactoryTalk Activation\ to inject malicious code that would execute with LocalSystem permissions. |
| A security issue in the runtime event system allows unauthenticated connections to receive a reusable API token. This token is broadcasted over a WebSocket and can be intercepted by any local client listening on the connection. |
| A denial-of-service security issue in the affected product. The security issue stems from a fault occurring when a crafted CIP unconnected explicit message is sent. This can result in a major non-recoverable fault. |
| A security issue was discovered in DataMosaix Private Cloud, allowing users with low privilege to perform sensitive database operations through exposed API endpoints. |
| A security issue exists in FactoryTalk ViewPoint version 14.0 or below due to improper handling of MSI repair operations. During a repair, attackers can hijack the cscript.exe console window, which runs with SYSTEM privileges. This can be exploited to spawn an elevated command prompt, enabling full privilege escalation. |
| A security issue was discovered within FactoryTalk® ViewPoint, allowing unauthenticated attackers to achieve XXE. Certain SOAP requests can be abused to perform XXE, resulting in a temporary denial-of-service. |
| A security issue exists due to improper handling of malformed CIP packets during fuzzing. The controller enters a hard fault with solid red Fault LED and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF019. To recover, clear the fault. |
| Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. |
| A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information. |
| A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information. |
| A memory abuse issue exists in the Rockwell Automation Arena® Simulation. A custom file can force Arena Simulation to read and write past the end of memory space. Successful use requires user action, such as opening a bad file or webpage. If used, a threat actor could execute code or disclose information. |
|
KEPServerEX does not properly validate certificates from clients which may allow unauthenticated users to connect.
|