Solution
Upgrade to P-Net 1.0.4 or later, which ignores alarm frames that do not come from the IO-controller of the Application Relationship. It reduces the risk but does not remove it, see Remaining Risk.
Workaround
Isolate the network of the device from untrusted hosts, for example by a firewall or a separate network,. The remaining risk is that a host on the network that knows the MAC address of the IO-controller and the alarm references can still send forged alarm frames.
Fri, 13 Nov 2026 16:45:00 +0000
| Type | Values Removed | Values Added |
|---|---|---|
| First Time appeared |
Rt-labs
Rt-labs p-net |
|
| Vendors & Products |
Rt-labs
Rt-labs p-net |
Fri, 13 Nov 2026 13:30:00 +0000
| Type | Values Removed | Values Added |
|---|---|---|
| Description | P-Net before 1.0.4 routes a received RTA alarm frame to an Application Relationship using only the destination alarm reference in the frame, without checking the source of the frame. A host with ADJACENT network access can abort an established Application Relationship with a single alarm ERROR frame, or deliver forged alarm notifications with chosen type, slot, subslot, USI and payload to the application. | |
| Title | Alarm frames are accepted from any source address | |
| Weaknesses | CWE-346 | |
| References |
| |
| Metrics |
cvssV4_0
|
Projects
Sign in to view the affected projects.
Status: PUBLISHED
Assigner: rt-labs
Published:
Updated: 2026-11-13T13:22:56.820Z
Reserved: 2026-11-09T12:48:59.071Z
Link: CVE-2026-124759
No data.
Status : Deferred
Published: 2026-11-13T14:17:50.337
Modified: 2026-11-13T14:17:50.433
Link: CVE-2026-124759
No data.
OpenCVE Enrichment
Updated: 2026-11-13T16:30:04Z